Manual – MOVI-PLC® advanced DH.41B Controller
6
Structure of the DP-V1 parameter channel
PROFIBUS-DP-V1 Functions
Processing
sequence for the
DP-V1 master
If the bus cycles are very short, the request for the parameter response arrives before
the MOVI-PLC
®
advanced DHF41B control card has concluded parameter access in the
device. This means that the response data from MOVI-PLC
®
advanced DHF41B is not
yet available. In this case, the MOVI-PLC
®
advanced DHF41B control card sends a
negative answer with the Error_Code _1 = 0xB5 (status conflict) to the DP-V1 level.
The DP-V1 master then repeats the request with the above Read.req header until it
receives a positive response from the MOVI-PLC
®
advanced DHF41B control card.
MOVILINK
®
parameter
requests
The MOVILINK
®
parameter channel of the MOVI-PLC
®
advanced DHF41B control card
is directly mapped in the structure of dataset 47. The Request ID 0x40 (SEW
MOVILINK
®
service) is used to exchange MOVILINK
®
parameter requests. Parameter
access with MOVILINK
®
services usually takes place according to the structure
described below. The typical message sequence for dataset 47 is used.
Request ID: 0x40 SEW MOVILINK® service
The actual service is defined by the dataset element Attribute in the MOVILINK
®
parameter channel. The high nibble of this element corresponds to the service nibble in
the management byte of the DP parameter channel.
53127AXX
Send Write.request
with Parameterdata
Send DS_Read.req
with Parameterdata
Check Write.
response
Write.response
negative
Write.response
positive
Parameter transfer
aborted with ERROR
Read.
response
State
Conflict?
Other Errors
or Timeout
yes
no
yes
no
Parameter transfer
ok, data available
00
I