TECHNICAL INFORMATION, INSTALLATION AND OPERATING INSTRUCTIONS Cabinet Warm Air Heater for oil burner BG SERIES All Parts available fr
RECEIPT OF THE PRODUCT The warm air heaters are supplied on wooden pallets (bolted to the heater) and are protected by a carton pack
HANDLING AND TRANSPORT Handling must be done by personnel with suitable equipment that has a lifting capacity adequate for the weight of the heater.
Installing examples MOUNTING THE DISTRIBUTION PLENUM The heater is supplied with a distribution plenum that is fitted with adjustab
112332On models type 1÷4 the plenum is already fitted on the heater. For transport reasons and/or for stacking, on models type 5÷7 the distribution
4132FITTING THE DOUBLE THERMOSTAT On models type 1÷4 the double thermostat is already fitted to the heater. Models type 5÷7 are supplied
SETTING THE DOUBLE THERMOSTAT The heater is supplied with the double thermostat already adjusted according to the following table: FAN Function 25
DUCTING A part of the heated air can be sent via ducting to other rooms using the pre-cut hole (ø 150 for type 1÷2; ø 300 for type 3÷7) at the top o
1200ELECTRIC CABLE ENTRY The electric cables connecting the heater must be adequately protected. To access the switchboard of the control panel, proce
DISCHARGE OF COMBUSTION PRODUCTS The flue ducts and the connection to the chimney must be built in conformity with current applicable
INSTALLATION OF THE BURNER For installing the burner, making the electrical connections and carrying out the necessary adjustments, refer to th
2 Dear Customer, We thank your for having chosen a BG series WARM AIR HEATER: an innovative product, both modern and of high quality, that will ens
IMPORTANT If the heater is replaced, but the existing burner continues to be used, make sure that: • The performance of the burner is coheren
mimino45°FIRST START-UP PREPARATION Before starting and testing warm air heaters, check that: • The protective film has been removed from t
10FIRST START-UP After carrying out the preparation operations for the first start-up, to start the warm air heater you must: Position the plant mai
In case of wrong switching on or working the generator will be able to make two different stop: 1. “BLOCK”, signalled by the luminous red push
CONTROLS ROOM THERMOSTAT This must be installed in the room to be heated at a height above floor level of 1.5 m approximately, i
2 1 2 98 761067431293851423 MAINTENANCE For good heater operation and conservation, we recommend you carry out periodical cleaning and
PERIODICAL FAN MAINTENANCE Type 1÷4 The motor is connected directly to the fan shaft. The fan motor does not need any maintenance, but only periodi
2 TROUBLE SHOOTING ANOMALY CAUSE REMEDIES THE GENERATOR DOES NOT WORK EITHER IN VENTILATION OR IN HEATING No energy supply Check
ANOMALY CAUSES REMEDIES THE BURNER GOES OUT ANOMALOUSLY AND BY CHANCE Actuation of the LIMIT thermostat Check the aperture of the a
2 ANOMALY CAUSES REMEDIES THE FAN DOES NOT STOP WITHIN FOUR MINUTES OF BURNER STOP Room temperature too high Check the inlet air te
INDEX GENERAL INFORMATION: RANGE 2 GUARANTEE 2 INDEX 3 GENERAL NOTES
3 NOTES 30 All Parts available from www.sparesgiant.com 01772 329 565
EC CONFORMITY DECLARATIONDÉCLARATION DE CONFORMITÉ À LA CEEU-ÜBEREINSTIMMUNGSERKLÄRUNGCONFORMITEITSVERKLARINGVOOR DE EUDICHIARAZIONE DI CONFORMITÀDECL
2 02/10_Rev.0 Cod. 745-MN DESA ITALIA s.p.a. Via Tione, 12 – 37010 P
GENERAL NOTES This Instruction Manual is an integral part of the device and as such must always be kept with the device. This is also the case wh
FUNDAMENTAL SAFETY RULES The use of devices that employ electrical energy and/or fuel oil requires the observance of some fundamental
5 54367109815111213142122162DESCRIPTION OF THE HEATER The warm air heater with fuel oil burner is a device that heats ambient air usin
Type 5÷7 1. Distribution plenum 2. Air delivery 3. Inspection doors 4. Burner plate 5. Air inlet 6. Flame inspection
IDENTIFICATION The BG warm air heater can be identified by the Technical Plate that shows the main technical and performance data. It if gets d
WIRING DIAGRAM Type 1÷4 Type 5÷7 G Three-phase fan motor RTV Fan motor thermal cut-out